The model VK506 is a cULus Listed and FM Approved, Early Suppression Fast Response (ESFR) type storage sprinkler capable of suppressing specific high-challenge fires. ESFR sprinklers can eliminate the use of in-rack sprinklers when protecting high-piled storage of certain specified materials up to:
UL: 40 ft. (12,2 m) with ceilings up to 45 ft. (13,7 m)*
FM: 45 ft. (13,7 m) with ceilings up to 50 ft. (15,2 m)*
They can also reduce or eliminate the need for a system fire pump and provide flexibility when sizing system piping. Viking VK506 ESFR Pendent Sprinklers are primarily intended to protect the following types of storage, which tend to produce severe-challenge fires: palletized and solid pile storage and single, double, multiple row, and portable open rack storage (no open-top containers or solid shelves).
* Refer Technical Data, Approval Charts and Commodity Selection and Design Criteria Overview for cULus Listing and FM Approval requirements that must be followed.
Technical Details
K Factor: 22.4, 320 metric
Manufacturer: Viking
Page: F_081612
Part Number: 18493, 18494
VK Number: VK506
Additional Information:
NOTICE: The product details indicated below are for general reference only and may vary based on the specific product approval and/or application. Always verify product details with the technical data sheet and consult with the Authority Having Jurisdiction (AHJ).
Max Pressure: 175 psi (12 bar)
Response Type: Fast (ESFR)
Occupancy Type: Storage
Thread Size: 1" NPT (25 mm BSP)
Min Spacing: Per Standards / Listings
Max Spacing: Per Standards / Listings